A Voltage Drop Calculator estimates the voltage lost in conductors carrying electrical current. Depending on the calculation method, it can express the loss in volts, as a percentage of source voltage and as an estimated voltage remaining at the load.

i The result depends on the circuit configuration and conductor assumptions. A correct calculation starts with a clear definition of cable length and the electrical path being assessed.

{{ panelTitle }}

{{ c.label }}
{{ c.hint }}
{{ c.suf }}
{{ c.sliderMin }}{{ c.sliderMax }}
{{ c.hint }}
{{ bigLabel }}
{{ bigValue }} {{ bigUnit }}
{{ bigSub }}
{{ st.label }} {{ st.value }}
Your calculation {{ wl }}

{{ resultNote }}

Same drop, different source voltages

{{ voltSub }} Select a row to use that voltage.

SourceShare of sourceDrop %

Changing source voltage alone does not change IR. It changes the percentage that the same loss represents. This holds current and resistance constant; it does not describe every real load.

Drop at other currents

For fixed impedance, drop scales with current. Select a row to use that current.

CurrentVoltage dropVolts

Steady running and starting conditions may differ. A load does not necessarily draw the same current when its terminal voltage changes.

01 — Definition

What is voltage drop?

Voltage drop is the difference in voltage associated with current flowing through resistance or impedance.

A cable has electrical resistance. When current flows, part of the source voltage appears across that resistance rather than across the load. AC circuits can also require consideration of reactance and power factor.

Scope

Cable calculations usually describe the selected conductors. They do not automatically include source-voltage variation, battery internal resistance, upstream wiring or contact resistance in switches and connections.

02 — Inputs

What information do you need?

InformationWhy it matters
Circuit typeDetermines the appropriate model
CurrentEstablishes the operating condition
Cable lengthDetermines conductor-path resistance or impedance
Conductor size and materialHelp establish electrical properties
Source voltageProvides the reference for percentage drop
Operating temperatureAffects conductor resistance
AC resistance, reactance and power factorMay be needed for an AC estimate

Some methods accept a known total resistance instead of deriving it from cable specifications. Others use manufacturer voltage-drop coefficients.

Do not assume that every voltage drop calculator supports all these approaches.

03 — Method

How to prepare a calculation

  1. 01

    Identify the circuit

    DC, two-wire single-phase AC or balanced three-phase AC.

  2. 02

    Check the length definition

    One-way route distance, one conductor’s length or total electrical path.

  3. 03

    Use the operating current being assessed

    Steady running and starting conditions may differ.

  4. 04

    Confirm conductor data

    Size, material, temperature and any impedance assumptions.

  5. 05

    Enter the appropriate source voltage

    Use a voltage reference consistent with the calculated drop.

  6. 06

    Interpret the result within its scope

    Check equipment requirements and the rest of the installation separately.

04 — Length

One-way length versus total circuit length

For a simple two-wire DC circuit, current travels through an outgoing conductor and a return conductor.

If both conductors have the same length and cross-sectional area, a 10 m one-way route contains 20 m of conductor in the complete loop.

However, do not automatically double every length input:

  • A one-way input may already receive a return-path adjustment inside the calculator.
  • A total-loop input must not be doubled again.
  • A known loop resistance already includes the specified path.
  • A chassis return or unequal conductors requires its own resistance assessment.

The correct treatment comes from the circuit and the calculator’s stated convention.

05 — DC formula

Voltage drop formula for DC circuits

When total path resistance is known:

ΔV = IRpath
Where:
ΔV
= voltage drop in volts.
I
= current in amperes.
Rpath
= total resistance of the path being assessed, in ohms.

For a uniform conductor segment:

R = ρLA
Where:
ρ
= resistivity at the stated conditions.
L
= length of that conductor segment.
A
= conducting cross-sectional area.

With resistivity in Ω·m, use length in metres and area in m². One mm² equals 10−6 m².

For equal outgoing and return conductors, their resistances can be added. If their properties differ, calculate the segments separately.

06 — Percentage

Voltage drop percentage and receiving-end voltage

Voltage drop (%) = ΔVVsource × 100

For the simple DC model:

Vload = Vsource − ΔV

This assumes the specified source voltage is available at the start of the assessed path and that current is known for the operating condition.

Load behaviour

A load does not necessarily draw the same current when its terminal voltage changes. Constant-power equipment, motors and other loads may require a more detailed assessment.

07 — Worked example

Worked example: a 12 V DC circuit

Assume:

  • Source voltage: 12 V.
  • Operating current: 5 A.
  • Total outgoing-and-return conductor resistance: 0.10 Ω.
  • No additional source or connection losses included.
Calculate the voltage drop ΔV = 5 × 0.10 = 0.50 V
Calculate the percentage (0.50 ÷ 12) × 100 ≈ 4.17%
Calculate the load voltage Vload = 12 − 0.50 = 11.50 V
ResultValue
Conductor voltage drop0.50 V
Percentage of source voltage4.17%
Estimated voltage at the load11.50 V

The resistance already represents both conductors, so no additional doubling is applied.

This example does not identify a wire gauge or establish that the circuit is suitable for its load.

08 — AC

How AC voltage drop differs

AC calculations may need both conductor resistance and reactance. Power factor determines how those components contribute to the approximate change in voltage magnitude.

For equal outgoing and return conductors in a simple two-wire single-phase circuit:

ΔV ≈ 2IL(r cos φ + x sin φ)

For a balanced three-phase circuit, the approximate line-to-line drop is:

ΔVLL ≈ √3 IL(r cos φ + x sin φ)
Where:
I
= circuit current; line current for the three-phase formula.
L
= one-way route length.
r
= resistance per unit length of one conductor.
x
= reactance per unit length.
cos φ
= power factor.
φ
= current phase angle relative to voltage.

Use matching units: resistance in Ω/km requires length in kilometres. These expressions assume an applicable steady-state model, with lagging current for the positive reactance contribution.

Schneider Electric’s steady-load voltage-drop guidance distinguishes these circuit relationships and their voltage references. Electrical Installation Guide

The formulas are approximations, not universal solutions for unbalanced systems, harmonics, distributed loads or every cable arrangement. Leading power factor also requires appropriate phase-angle treatment.

Three-phase reference

For balanced three-phase percentage drop, use the corresponding line-to-line source voltage. Do not divide line-to-line drop by line-to-neutral voltage.

09 — Factors

What changes the result?

FactorEffect under otherwise unchanged assumptions
Longer conductor pathIncreases resistance and generally increases drop
Higher currentIncreases drop for fixed impedance
Larger conducting areaGenerally reduces resistance
Different materialChanges resistance
Higher conductor temperatureTypically increases resistance for copper and aluminum
Different circuit configurationChanges the calculation relationship
AC power factor and reactanceAffect the approximate AC result

Changing source voltage alone does not change IR when current and resistance remain fixed. It does change the percentage that the same voltage loss represents.

For example, a 0.50 V drop is approximately 4.17% of 12 V but 2.08% of 24 V. This comparison holds current and resistance constant; it does not describe every real load.

10 — Limits

What voltage drop is acceptable?

There is no single percentage that establishes suitability or compliance for every circuit.

Assess:

  • Equipment operating-voltage requirements.
  • Steady-state and starting conditions.
  • Drop already present in upstream conductors.
  • Applicable design guidance and electrical requirements.
  • The relevant jurisdiction and installation type.

For US work, verify the adopted NEC edition and applicable provisions. For UK work, verify the applicable BS 7671 guidance and project conditions. A general percentage target should not be presented as a universal legal limit.

Southwire’s voltage-drop tool guidance distinguishes installation modes and assumptions, illustrating why results must be interpreted within their intended application. Southwire

!

A low voltage-drop result does not independently establish ampacity, protective-device suitability, fault protection or installation safety.

11 — Mistakes

Common calculation mistakes

MistakeBetter approach
×Doubling a length already entered as total path→Read the length convention first
×Omitting the return conductor in a DC loop→Assess the complete electrical path
×Mixing Ω/km with metres→Convert units before multiplying
×Treating diameter as area→Distinguish mm from mm²
×Using DC resistance as a complete AC model→Check impedance and power-factor assumptions
×Using the wrong three-phase voltage reference→Match line-to-line quantities
×Ignoring upstream voltage loss→Define the start and end of the assessment
×Treating a percentage result as a safety certificate→Complete the other electrical checks