Wire Gauge Calculator

A Wire Gauge Calculator helps interpret conductor size, commonly by converting American Wire Gauge (AWG) into bare-conductor diameter and cross-sectional area.

i These measurements describe the conductor—not the outside of its insulation and not a universal current rating. Before comparing results, check the gauge system, conductor construction and units.

Conductor size

{{ c.label }}
{{ c.hint }}
{{ c.suf }}
{{ c.sliderMin }}{{ c.sliderMax }}
{{ c.hint }}
{{ bigLabel }}
{{ bigValue }} {{ bigUnit }}
{{ bigSub }}
{{ st.label }} {{ st.value }}
Your calculation {{ wl }}

Nominal bare solid-conductor geometry. Not insulated or cable diameter, and not a current rating. Gauge does not determine safe amperage by itself.

Cross-sections to scale

Three AWG numbers apart. Area roughly doubles; diameter does not.

{{ ci.label }} {{ ci.sub }}

A decrease of three AWG numbers approximately doubles conducting area. It does not double diameter; area depends on diameter squared.

Nearby gauges

Calculated nominal solid-conductor values. Select a row to convert that gauge.

AWGDia · mmDia · inArea · mm²

These are not ampacity values or exact outside diameters for insulated products.

01 — AWG

What does AWG tell you?

American Wire Gauge is a stepped size system commonly used for electrical conductors in North America. A lower AWG number represents a larger conductor.

For example, 12 AWG has more conducting area than 18 AWG. Gauge numbers are not linear measurements: 12 AWG does not mean a 12 mm diameter.

Metric cable specifications commonly identify conductor area in square millimeters, particularly in the UK and other markets. Comparing those specifications requires an area conversion, not simply a diameter comparison.

Equivalent is not interchangeable

A rounded AWG-to-metric equivalent is dimensional information. It does not automatically establish that two cables are interchangeable in an installation.

02 — Measurements

Diameter, conducting area and cable diameter

MeasurementMeaning
{{ ir.a }}{{ ir.b }}

For stranded wire, gaps and strand arrangement affect the bundle’s outside dimensions. Treating that entire bundle as a solid metal circle can overstate its conducting area.

Likewise, measuring insulation with calipers does not identify the bare conductor’s AWG.

03 — Method

How to use a wire gauge conversion

  1. {{ sp.n }}

    {{ sp.title }}

    {{ sp.text }}

04 — Formula

AWG diameter formula

For the nominal diameter of a solid round conductor:

dmm = 0.127 × 92(36 − n)/39
Where:
dmm
= diameter in millimeters.
n
= AWG gauge number.
The equivalent inch formula is: din = 0.005 × 92(36 − n)/39

DigiKey’s AWG conversion reference provides these dimensional relationships and identifies its conversions as solid-wire based. DigiKey

For the larger “aught” sizes, the formula uses:

Gauge labelValue of n
{{ ar.a }}{{ ar.b }}
Not a fraction

Do not enter “2/0” as an ordinary arithmetic fraction.

05 — Area

Converting diameter into cross-sectional area

For a solid circular conductor:

A=πd24

When d is in millimeters, A is in square millimeters.

For stranded construction, conducting area is based on the metal in the strands rather than the outside diameter of the bundle. Product specifications remain the appropriate reference for the finished conductor.

06 — Worked example

Worked example: 18 AWG

Using n = 18 d = 0.127 × 92(36 − 18)/39 d ≈ 1.023687 mm
Then A = π(1.023687)² ÷ 4 ≈ 0.823047 mm²
ResultRounded value
Nominal solid-conductor diameter1.024 mm
Diameter in inches0.04030 in
Cross-sectional area0.823 mm²

The example illustrates dimensional conversion only. It does not assign a safe operating current.

07 — Reference

Short AWG conversion table

The following values were calculated using the formulas above and rounded for reference. Diameter represents a solid circular conductor or an equivalent solid-circle geometry.

AWGDiameter, mmDiameter, inArea, mm²
{{ rt.a }}{{ rt.b }}{{ rt.c }}{{ rt.d }}

These are not ampacity values or exact outside diameters for insulated products.

A decrease of three AWG numbers approximately doubles conducting area. It does not double diameter; area depends on diameter squared.

08 — Resistance

How conductor size affects resistance

Larger areaGenerally lower resistance
Longer conductorGenerally higher resistance

With material, length and temperature held constant, a larger conducting area generally gives lower resistance. A longer conductor generally gives higher resistance.

Material matters too. Copper and aluminum have different electrical properties, so equal dimensions do not establish equal resistance or interchangeable installation requirements.

Temperature and conductor construction also affect electrical performance.

09 — Amperage

Gauge does not determine safe amperage by itself

Allowable current depends on the complete installation, including conductor material, insulation rating, ambient conditions, grouping, terminations and applicable rules.

{{ af }}

Southwire’s building-wire specification distinguishes temperature-dependent ratings and identifies additional protection limitations. It illustrates why one gauge cannot be assigned a universal current limit. Southwire

Voltage drop is a separate assessment. It depends on current, conductor properties, circuit length and configuration. In a simple two-wire DC circuit, both outgoing and return conductor lengths contribute to the loop; three-phase AC circuits require different treatment.

!

Follow applicable local electrical requirements and manufacturer specifications. For safety-critical conductor selection, use a qualified electrician or electrical designer rather than a dimensional conversion alone.

10 — Mistakes

Common wire-sizing mistakes

MistakeBetter approach
×{{ mk.m }} →{{ mk.b }}
11 — FAQ

Frequently asked questions

{{ q.a }}

12 — Sources

External references

Related calculators

More Electrical Tools

All electrical calculators →